How It Works
Wire sizing needs two checks: ampacity (how much current the wire can safely carry, from NEC 310.16) and voltage drop (keeping it under ~3% for branch circuits). This calculator applies both and picks the larger gauge.
Calculation Explanation
Example: 30A, 120V, 50 ft, copper. Ampacity says #10 (30A limit). Voltage drop for #10 at 50 ft ≈ 2.5% — within range. For 100 ft it would exceed 3%, so the tool bumps to #8.
Related: check your circuit's breaker size or estimate voltage drop for an existing run.
Wire Size Quick Reference (Copper)
| AWG | Max Amps (copper) | Common Use |
|---|---|---|
| 14 | 15 | Lights, 15A outlets |
| 12 | 20 | Kitchen / bath / garage outlets |
| 10 | 30 | Dryer, water heater, AC (30A) |
| 8 | 40 | Ranges, EV chargers (40A) |
| 6 | 55 | EV chargers, subpanels (50–60A) |
| 4 | 70 | Large subpanels, welders (70A) |