Voltage Drop Calculator

Check how much voltage you lose over a wire run. Enter gauge, current, one-way length, and voltage to see volts and percent drop — and whether you pass the 3% guideline.

Voltage drop
5.29% (6.35 V)
Over 5% — serious risk, use larger wire or shorter run.

How It Works

Every conductor has resistance per foot. Multiply by the total path length (out and back, hence factor 2) and current to get volts lost: VD = 2 × R × L × I. Percent drop is VD ÷ system voltage.

Calculation Explanation

Example: #12 copper, 20A, 100 ft, 120V → 2 × 1.588/1000 × 100 × 20 = 6.35V → 5.3% drop. That's why a 120V 20A circuit shouldn't run 100 ft on #12 — bump to #10 (3.3%).

If the drop is too high, use the Wire Size Calculator to pick a bigger gauge, or check the breaker size for the circuit.

Voltage Drop Quick Reference (Copper, 3% target)

AWG15A @ 120V20A @ 120V30A @ 240V
#14~50 ft
#12~75 ft~55 ft
#10~120 ft~90 ft~170 ft
#8~190 ft~140 ft~270 ft
#6~225 ft~430 ft